Technical details

Leak monitoring system

s

Vacuum leak detector type VLX 330/A-Ex

Laying in one line up to max. 10 bar

Connecting the leak detector to the surveillance space

of the double-walled piping (Worksheet LDS 8.232

)

A test valve must be installed at the far end of the pipe. The low point(s) must no

t

exceed a depth of 3.5 m. The piping can have further high or low points as long a

s

the sum of the high and low points does not exceed 3.5 m

.