Technical details

Leak monitoring system

s

Vacuum leak detector type VLR 410 PMMV Si

Laying in a single line up to max. 25 ba

r

Connecting the leak detector to the surveillance spac

e

of the double-walled safety pipe (Worksheet LDS 8.213)

A test valve must be installed at the far end of the pipe. The low point(s) must not ex

-

ceed a depth of 3.5 m. The piping can have further high or low points as long as th

e

sum of the high and low points doues not exceed 3.5 m

.

MA

Mesauring branc

h

AV

connection fittin

g

PV

test valv

e

KP

cross poin

t

PB

transport pressure in inner pip

e

MV

solenoid valv

e

FL

fluid barrie

r

LD

S

8.214

shut

BV

GD

FL

KP

ope

n

P

V

P < 5 bar

M

A

m

a

x

.

3

.

0

m

m

a

x

.

3

.

5

m

A

V

P

V

A

V

A

V

P

V

A

V

m

a

x

.

2

5

0

m

BV

shu

t GD

open

K

P

MA

31.03.2026 Subject to technical changes. Page 1

0

m

a

x

.

3

.

5

m

A

V

m

a

x

.

3

.

0

m

At a PB > 5 bar up to max. 25 bar a

solenoid valve MV must be installed

between the crosspoint KP and th

e

measuring branch MA

.

The solenoid valve protects the

leak detector from non-permissible

high pressures. The solenoid valve

is monitored electronically so that

a failure of the solenoid valve

triggers the alarm.