Technical details
Connecting the leak detector to the surveillance spac
e
of the double-walled safety pipe (Worksheet LDS 8.213)
A test valve must be installed at the far end of the pipe. The low point(s) must not ex
-
ceed a depth of 3.5 m. The piping can have further high or low points as long as th
e
sum of the high and low points doues not exceed 3.5 m
.
MA
Mesauring branc
h
AV
connection fittin
g
PV
test valv
e
KP
cross poin
t
PB
transport pressure in inner pip
e
MV
solenoid valv
e
FL
fluid barrie
r
shut
FL
KP
ope
n
P
V
P < 5 bar
M
A
m
a
x
.
3
.
0
m
m
a
x
.
3
.
5
m
A
V
P
V
A
V
A
V
P
V
A
V
m
a
x
.
2
5
0
m
BV
shu
t GD
open
K
P
MA
31.03.2026 Subject to technical changes. Page 1
0
m
a
x
.
3
.
5
m
A
V
m
a
x
.
3
.
0
m
At a PB > 5 bar up to max. 25 bar a
solenoid valve MV must be installed
between the crosspoint KP and th
e
measuring branch MA
.
The solenoid valve protects the
leak detector from non-permissible
high pressures. The solenoid valve
is monitored electronically so that
a failure of the solenoid valve
triggers the alarm.