290

DATI DI CAPACITÀ ED EFFICIENZA IN FUNZIONE DELLA TEMPERATURA ESTERNA SECONDO LA NORMA EN14511-3:2018

GRS-CQ6.0Pd/NpG4-E

RISCALDAMENTO - Temperatura dell’aria esterna a bulbo secco in °C

-25

-20

-15

-10

-7

-2

2

7

10

15

20

25

30

35

LW

T

[°C]

Qh

[kW]

COP

[kW]

Q

h

COP

[kW]

Q

h

COP

[kW]

Qh

COP

[kW]

Q

h

COP

[kW]

Q

h

COP

[kW]

Qh

COP

[kW]

Q

h

COP

[kW]

Q

h

COP

[kW]

Qh

COP

[kW]

Qh

COP

[kW]

Qh

COP

[kW]

Qh

COP

[kW]

Q

h

COP

25 3.33 1.94 3.56 2.28 4.26 2.63 5.28 3.16 5.73 3.74 5.43 4.09 5.57 4.54 6.08 6.10 6.20 6.25 6.42 6.69 6.59 6.94 6.91 7.45 6.96 7.77 7.01 8.1

0

30 3.36 1.78 3.60 2.10 4.30 2.41 5.33 2.90 5.79 3.43 5.48 3.76 5.62 4.17 6.14 5.60 6.26 5.74 6.49 6.14 6.66 6.37 6.99 6.84 7.03 7.14 7.08 7.4

3

35 3.48 1.59 3.71 1.87 4.35 2.15 5.08 2.59 5.50 3.07 5.61 3.36 5.75 3.72 6.20 5.00 6.32 5.13 6.56 5.48 6.78 5.69 7.06 6.11 7.15 6.37 7.35 6.6

4

40 3.40 1.40 3.63 1.65 4.35 1.89 5.39 2.28 5.84 2.70 5.54 2.95 5.68 3.28 6.20 4.40 6.32 4.51 6.56 4.82 6.73 5.00 7.06 5.37 7.11 5.61 7.15 5.8

4

45 3.34 1.24 3.58 1.46 4.28 1.68 5.30 2.02 5.75 2.39 5.45 2.62 5.59 2.90 6.10 3.90 6.22 4.00 6.45 4.27 6.62 4.44 6.94 4.76 6.99 4.97 7.04 5.1

8

50 3.33 1.19 3.56 1.40 4.26 1.61 5.28 1.94 5.73 2.30 5.43 2.52 5.57 2.79 6.08 3.75 6.20 3.84 6.42 4.11 6.59 4.27 6.91 4.58 6.96 4.78 7.01 4.9

8

55 3.01 1.11 3.22 1.31 3.85 1.51 4.78 1.81 5.18 2.15 4.91 2.35 5.04 2.61 5.50 3.50 5.61 3.59 5.81 3.84 5.97 3.98 6.26 4.27 6.30 4.46 6.35 4.6

5

60

/

/ 2.94 1.05 3.52 1.21 4.36 1.45 4.73 1.72 4.49 1.88 4.60 2.09 5.02 2.80 5.12 2.87 5.31 3.07 5.45 3.18 5.72 3.42 5.76 3.57 5.79 3.7

2

65

/

/ 2.83 0.94 3.39 1.08 4.20 1.29 4.56 1.53 4.32 1.68 4.43 1.86 4.84 2.50 4.93 2.56 5.11 2.74 5.25 2.84 5.50 3.05 5.54 3.19 /

/

70

/

/

/

/ 3.26 0.95 4.04 1.14 4.38 1.35 4.15 1.48 4.26 1.64 4.65 2.20 4.74 2.26 4.92 2.41 5.04 2.50 5.29 2.69 /

/

/

/

75

/

/

/

/

/

/ 3.93 1.09 4.27 1.29 4.04 1.41 4.15 1.56 4.53 2.10 4.62 2.15 4.79 2.30 4.91 2.39 /

/

/

/

/

/

80

/

/

/

/

/

/

/

/ 4.03 1.13 3.82 1.24 3.92 1.38 4.28 1.85 /

/

/

/

/

/

/

/

/

/

/

/

RAFFREDDAMENTO - Temperatura dell’aria esterna a bulbo secco in °C

-15

-10

-5

0

5

10

15

20

25

30

35

40

45

48

LW

T

[°C]

Qc

[kW]

EER

[kW]

Q

c

EER

[kW]

Q

c

EER

[kW]

Q

c

EER

[kW]

Q

c

EER

[kW]

Q

c

EER

[kW]

Qc

EER

[kW]

Qc

EER

[kW]

Qc

EER

[kW]

Qc

EER

[kW]

Q

c

EER

[kW]

Qc

EER

[kW]

Qc

EER

[kW]

Qc

EE

R

7 4.51 5.95 4.31 6.63 4.10 7.31 3.90 7.48 4.32 6.29 5.88 6.13 5.59 5.53 5.36 4.96 5.83 4.34 5.56 3.81 6.10 3.20 5.34 2.77 4.54 2.19 4.16 1.7

8

8 4.51 6.37 4.31 7.09 4.10 7.82 3.90 8.00 4.32 6.73 5.88 6.56 5.59 5.91 5.36 5.31 5.83 4.64 5.56 4.07 6.10 3.42 5.34 2.97 4.54 2.34 4.16 1.9

0

9 4.51 6.78 4.31 7.56 4.10 8.33 3.90 8.53 4.32 7.17 5.88 6.99 5.59 6.30 5.36 5.65 5.83 4.94 5.56 4.34 6.10 3.65 5.34 3.16 4.54 2.50 4.16 2.0

3

10 4.51 7.20 4.31 8.02 4.10 8.85 3.90 9.05 4.32 7.61 5.88 7.42 5.59 6.69 5.36 6.00 5.83 5.25 5.56 4.61 6.10 3.87 5.34 3.35 4.54 2.65 4.16 2.1

5

11 4.56 7.62 4.35 8.49 4.14 9.36 3.93 9.57 4.36 8.05 5.93 7.85 5.65 7.08 5.41 6.35 5.89 5.55 5.62 4.87 6.16 4.10 5.39 3.55 4.58 2.80 4.20 2.2

8

12 4.56 8.03 4.35 8.95 4.14 9.87 3.93 10.10 4.36 8.49 5.93 8.28 5.65 7.46 5.41 6.69 5.89 5.85 5.62 5.14 6.16 4.32 5.39 3.74 4.58 2.95 4.20 2.4

0

13 4.57 8.45 4.36 9.41 4.15 10.38 3.95 10.62 4.38 8.93 5.95 8.71 5.67 7.85 5.43 7.04 5.91 6.16 5.63 5.41 6.18 4.54 5.41 3.94 4.59 3.11 4.21 2.5

3

14 4.65 8.87 4.43 9.88 4.22 10.89 4.01 11.15 4.45 9.37 6.05 9.13 5.76 8.24 5.52 7.39 6.01 6.46 5.73 5.67 6.28 4.77 5.50 4.13 4.67 3.26 4.28 2.6

5

15 4.69 9.28 4.48 10.34 4.26 11.40 4.05 11.67 4.49 9.81 6.11 9.56 5.82 8.62 5.57 7.73 6.07 6.76 5.78 5.94 6.34 4.99 5.55 4.32 4.72 3.41 4.32 2.7

7

18 4.58 9.67 4.37 10.77 4.17 11.88 3.96 12.16 4.39 10.22 5.97 9.96 5.68 8.98 5.44 8.06 5.93 7.05 5.65 6.19 6.20 5.20 5.42 4.50 4.61 3.56 4.22 2.8

9

20 4.65 9.88 4.43 11.01 4.22 12.13 4.01 12.42 4.45 10.44 6.05 10.18 5.76 9.18 5.52 8.23 6.01 7.20 5.73 6.32 6.28 5.31 5.50 4.60 4.67 3.63 4.28 2.9

5

23 4.65 10.06 4.43 11.20 4.22 12.35 4.01 12.64 4.45 10.63 6.05 10.36 5.76 9.34 5.52 8.38 6.01 7.33 5.73 6.43 6.28 5.41 5.50 4.69 4.67 3.70 4.28 3.0

1

25 4.69 10.17 4.48 11.34 4.26 12.50 4.05 12.79 4.49 10.76 6.11 10.48 5.82 9.45 5.57 8.48 6.07 7.41 5.78 6.51 6.34 5.47 5.55 4.74 4.72 3.74 4.32 3.0

4

LWT: temperatura di uscita dell’acqu

a

Qh: capacità di riscaldament

o

COP: coe

fficiente di prestazione

LWT: temperatura di uscita dell’acqua

Qc: capacità di raffreddamento

EER: indice di efficienza energetica

9