290

DATI DI CAPACITÀ ED EFFICIENZA IN FUNZIONE DELLA TEMPERATURA ESTERNA SECONDO LA NORMA EN14511-3:2018

GRS-CQ8.0Pd/NpG4-E

RISCALDAMENTO - Temperatura dell’aria esterna a bulbo secco in °C

-25

-20

-15

-10

-7

-2

2

7

10

15

20

25

30

35

LW

T

[°C]

Qh

[kW]

COP

[kW]

Q

h

COP

[kW]

Q

h

COP

[kW]

Qh

COP

[kW]

Q

h

COP

[kW]

Q

h

COP

[kW]

Qh

COP

[kW]

Q

h

COP

[kW]

Q

h

COP

[kW]

Qh

COP

[kW]

Qh

COP

[kW]

Qh

COP

[kW]

Qh

COP

[kW]

Q

h

COP

25 4.05 1.94 4.33 2.28 5.17 2.63 6.29 3.08 6.86 3.65 7.03 4.02 7.21 4.46 8.23 5.99 8.40 6.14 8.45 6.54 8.67 6.79 9.26 7.34 9.32 7.66 9.39 7.9

8

30 4.09 1.78 4.37 2.10 5.23 2.41 6.36 2.83 6.93 3.35 7.10 3.69 7.29 4.09 8.32 5.50 8.48 5.64 8.54 6.01 8.76 6.23 9.35 6.74 9.42 7.03 9.48 7.3

2

35 4.13 1.59 4.42 1.87 5.28 2.15 6.42 2.53 7.00 3.00 7.18 3.29 7.36 3.66 8.40 5.00 8.57 5.03 8.63 5.36 8.85 5.57 9.45 6.01 9.51 6.28 9.58 6.5

4

40 4.13 1.40 4.42 1.65 5.28 1.89 6.42 2.22 7.00 2.64 7.18 2.90 7.36 3.22 8.40 4.32 8.57 4.43 8.63 4.72 8.85 4.90 9.45 5.29 9.51 5.52 9.58 5.7

5

45 4.13 1.34 4.42 1.57 5.28 1.81 6.42 2.12 7.00 2.50 7.18 2.77 7.36 3.07 8.40 3.90 8.57 4.23 8.63 4.51 8.85 4.68 9.45 5.05 9.51 5.27 9.58 5.4

9

50 4.05 1.26 4.33 1.48 5.17 1.70 6.29 2.00 6.86 2.37 7.03 2.60 7.21 2.89 8.23 3.88 8.40 3.98 8.45 4.24 8.67 4.40 9.26 4.75 9.32 4.96 9.39 5.1

6

55 3.54 1.18 3.79 1.39 4.53 1.59 5.51 1.87 6.00 2.20 6.16 2.44 6.31 2.71 7.20 3.60 7.35 3.72 7.40 3.97 7.59 4.12 8.11 4.45 8.16 4.64 8.22 4.8

4

60

/

/ 3.74 1.05 4.48 1.21 5.45 1.42 5.93 1.68 6.09 1.85 6.24 2.05 7.12 2.75 7.27 2.82 7.31 3.00 7.50 3.12 8.01 3.37 8.07 3.51 8.12 3.6

6

65

/

/ 3.70 0.94 4.42 1.08 5.38 1.26 5.86 1.50 6.01 1.65 6.17 1.83 7.04 2.46 7.18 2.52 7.23 2.68 7.42 2.78 7.92 3.01 7.97 3.14 /

/

70

/

/

/

/ 4.37 0.95 5.32 1.11 5.79 1.32 5.94 1.45 6.09 1.61 6.96 2.16 7.09 2.21 7.14 2.36 7.33 2.45 7.82 2.65 /

/

/

/

75

/

/

/

/

/

/ 5.25 1.06 5.72 1.26 5.87 1.38 6.02 1.54 6.87 2.06 7.01 2.11 7.06 2.25 7.24 2.34 /

/

/

/

/

/

80

/

/

/

/

/

/

/

/ 5.65 1.06 5.80 1.17 5.95 1.30 6.79 1.74 /

/

/

/

/

/

/

/

/

/

/

/

RAFFREDDAMENTO - Temperatura dell’aria esterna a bulbo secco in °C

-15

-10

-5

0

5

10

15

20

25

30

35

40

45

4

8

LW

T

[°C]

Qc

[kW]

EER

[kW]

Q

c

EER

[kW]

Q

c

EER

[kW]

Q

c

EER

[kW]

Q

c

EER

[kW]

Q

c

EER

[kW]

Qc

EER

[kW]

Qc

EER

[kW]

Qc

EER

[kW]

Qc

EER

[kW]

Q

c

EER

[kW]

Qc

EER

[kW]

Qc

EER

[kW]

Qc

EE

R

7 5.59 5.93 5.33 6.61 5.08 7.29 4.83 7.46 4.67 6.25 7.04 6.09 6.70 5.49 6.42 4.93 6.44 4.32 6.14 3.80 7.50 3.20 5.18 2.76 4.08 2.18 3.74 1.7

7

8 5.70 6.35 5.44 7.07 5.18 7.80 4.92 7.98 4.76 6.69 7.18 6.52 6.83 5.88 6.55 5.27 6.57 4.63 6.26 4.06 7.65 3.42 5.28 2.96 4.16 2.34 3.82 1.9

0

9 5.76 6.76 5.49 7.54 5.23 8.31 4.97 8.50 4.81 7.13 7.25 6.95 6.90 6.26 6.61 5.62 6.63 4.93 6.32 4.33 7.73 3.65 5.33 3.15 4.20 2.49 3.85 2.0

2

10 5.81 7.18 5.55 8.00 5.28 8.82 5.02 9.02 4.86 7.57 7.32 7.37 6.97 6.65 6.67 5.96 6.69 5.23 6.38 4.59 7.80 3.87 5.39 3.34 4.25 2.64 3.89 2.1

5

11 5.87 7.59 5.60 8.46 5.33 9.33 5.07 9.55 4.90 8.00 7.39 7.80 7.03 7.03 6.74 6.31 6.76 5.53 6.45 4.86 7.88 4.10 5.44 3.54 4.29 2.79 3.93 2.2

7

12 5.92 8.01 5.65 8.92 5.38 9.84 5.12 10.07 4.95 8.44 7.46 8.23 7.10 7.42 6.80 6.65 6.82 5.84 6.51 5.12 7.95 4.32 5.49 3.73 4.33 2.95 3.97 2.3

9

13 5.98 8.42 5.71 9.39 5.44 10.35 5.16 10.59 5.00 8.88 7.53 8.65 7.17 7.80 6.87 7.00 6.89 6.14 6.57 5.39 8.03 4.54 5.54 3.92 4.37 3.10 4.00 2.5

2

14 6.04 8.84 5.76 9.85 5.49 10.86 5.21 11.11 5.04 9.32 7.60 9.08 7.24 8.19 6.93 7.34 6.95 6.44 6.63 5.65 8.10 4.77 5.59 4.12 4.41 3.25 4.04 2.6

4

15 6.09 9.25 5.81 10.31 5.54 11.37 5.26 11.63 5.09 9.75 7.67 9.51 7.30 8.57 7.00 7.69 7.02 6.74 6.69 5.92 8.18 4.99 5.65 4.31 4.45 3.40 4.08 2.7

7

18 6.18 9.64 5.90 10.74 5.62 11.84 5.34 12.12 5.17 10.16 7.78 9.90 7.41 8.93 7.10 8.01 7.12 7.02 6.79 6.17 8.30 5.20 5.73 4.49 4.52 3.55 4.14 2.8

8

20 6.31 9.85 6.03 10.97 5.74 12.10 5.45 12.38 5.28 10.38 7.95 10.12 7.57 9.12 7.25 8.18 7.27 7.18 6.94 6.30 8.48 5.31 5.85 4.59 4.61 3.62 4.23 2.9

4

23 6.43 10.03 6.13 11.17 5.84 12.32 5.55 12.60 5.37 10.57 8.09 10.30 7.70 9.29 7.38 8.33 7.40 7.31 7.06 6.41 8.63 5.41 5.96 4.67 4.69 3.69 4.30 3.0

0

25 6.54 10.14 6.24 11.30 5.94 12.46 5.65 12.75 5.47 10.69 8.23 10.42 7.84 9.40 7.51 8.43 7.53 7.39 7.18 6.49 8.78 5.47 6.06 4.73 4.78 3.73 4.38 3.0

3

LWT: temperatura di uscita dell’acqu

a

Qh: capacità di riscaldament

o

COP: coe

fficiente di prestazione

LWT: temperatura di uscita dell’acqua

Qc: capacità di raffreddamento

EER: indice di efficienza energetica

11