SDR 1
1
Perdite termiche q [W/m] per un tubo UNO
Tipo
Valore U Temperatura d'esercizio media TB [°C
]
[W/mK]
4°
8°
12°
16°
20°
1125/225
0.238
–1.4
–0.5
0.5
1.4
2.
4
140/225
0.286
–1.7
–0.6
0.6
1.7
2.
9
160/250
0.302
–1.8
–0.6
0.6
1.8
3.
0
180/280
0.306
–1.8
–0.6
0.6
1.8
3.
1
200/315
0.300
–1.8
–0.6
0.6
1.8
3.
0
225/315
0.383
–2.3
–0.8
0.8
2.3
3.
8
250/355
0.373
–2.2
–0.8
0.8
2.2
3.
7
280/400
0.370
–2.2
–0.7
0.7
2.2
3.
7
a
a
=
= 0,1 m
0,1
m
315/450
0.371
–2.2
–0.7
0.7
2.2
3.
7
355/500
0.380
–2.3
–0.8
0.8
2.3
3.
8
H
=
H
0
,
8
m
=
0
,
6
m
400/560
0.387
–2.3
–0.8
0.8
2.3
3.
9
450/630
0.388
–2.3
–0.8
0.8
2.3
3.
9
315/450
0,370
–1,5
–0,7
0,0
0,7
1,5
SDR 1
7
Perdite termiche q [W/m] per un tubo UNO
Tipo
Valore U Temperatura d'esercizio media TB [°C
]
[W/mK]
4°
8°
12°
16°
20°
125/225
0.240
–1.4
–0.5
0.5
1.4
2.4
140/225
0.288
–1.7
–0.6
0.6
1.7
2.9
160/250
0.304
–1.8
–0.6
0.6
1.8
3.0
180/280
0.308
–1.9
–0.6
0.6
1.9
3.1
200/315
0.303
–1.8
–0.6
0.6
1.8
3.0
225/315
0.387
–2.3
–0.8
0.8
2.3
3.9
250/355
0.377
–2.3
–0.8
0.8
2.3
3.8
280/400
0.374
–2.2
–0.8
0.8
2.2
3.7
315/450
0.375
–2.3
–0.8
0.8
2.3
3.8
355/500
0.385
–2.3
–0.8
0.8
2.3
3.9
400/560
0.392
–2.4
–0.8
0.8
2.4
3.9
450/630
0.393
–2.4
–0.8
0.8
2.4
3.9
315/450
0,374
–1,5
–0,7
0,0
0,7
1,5
Tipo di posa COOLMANT
:
Distanza tra i tubi
:
Altezza reinterro
:
Temperatura del terreno:
Conducibilità del terreno:
Conducibilità della schiuma in PUR
:
Conducibilità del tubo in PE
:
Conducibilità della guaina in PE
:
2 tubi interrati
a = 0,10 m
H = 0,80 m
lPU = 0,026 W/mK
lPE = 0,40 W/m
K
lPE = 0,33 W/m
K
Dispersione termica in esercizio
:
q = U (TB -TE) [W/m]
U = dispersione termica unitaria [W/mK]
VL = mandat
a
RL = ritorno
Su richiesta possibilità di calcolare anche le dispersioni termiche dei sistemi di tubazioni
posati in esterno.
25.02.2026 | con riserva di modifiche tecniche.