Technical details
Pos No. of component to be checked
functions well
defectiv
e
1
Vacuum pump
2
Vacuum switch
Switching levels:
VLR 410 PMMV Si and VLR 410/E / VLX 330/A-E
x
pump “o
ff” < 540 mbar / < 540 mba
r
pump “on” the level must be at least 15 mbar higher than the
switching level measured for “Alarm on”
Alarm “on” > 410 mbar / > 330 mba
r
3
Filter with non-return valv
e
tight
untigh
t
4
Screw connections: ventilation screw and three-way stopcoc
k
5
Screw connections underneath the leak detector
6
Screw connections:
fluid barriers
7
T-piece in the connection pipes – single-line system – *
8/9
All screw connections: long nipple/test valve
* also in multiple
-
line syste
m
with distributor
block
10
All screw connections: measuring branch
11
Pressure test of individual lines: surveillance space
When piping is untigh
t
12
Screw socket, inner weld seams / GRAPA
13
Screw socket, outer weld seams / GRAPA
14
Screw socket, all
fitting drill hole
s
Put into operation
yes
n
o
surveillance space – clear passa
g
existing defects rectifie
d
Plant put into operatio
n
Vacuum leak detector under sea
l
Stamp
/
Date:
Signature
:
31.03.2026 Subject to technical changes. Page 34